CONTAINERIZED TYPE DIESEL GENERATOR SETS--CUMMINS SERIES

Product Description

 GENERATOR SETS POWERED BY CUMMINS ENGINE


MAIN SPECIFICATION OF DIESEL GENERATOR SETS (50HZ)
GENSET
MODEL
Soundproof model GDC625S GDC725S GDC750S GDC800S GDC910S GDC1000S GDC1125S GDC1250S GDC1375S GDC1500S
Prime output(kVA/kW) 625/500 725/580 750/600 800/640 910/728 1000/800 1125/900 1250/1000 1375/1100 1500/1200
Standby output (kVA/kW) 687/550 800/640 825/660 880/704 1000/800 1100/880 1250/1000 1375/1100 1512/1210 1650/1320


TECHNICAL DATA
DIESEL ENGINE MODEL KT38-G KT38-GA KTA38-G2 KTA38-G2B KTA38-G2A KTA38-G5 KTA38-G9 KTA50-G3 KTA50-G8 KTA50-GS8
ENGINE CHARACTERS Water-cooled, 60° Vee,4-stroke,direct injection,wet cylinder liner,1500rpm
Prime Output (KW) 560 N/A 664 711 813 880 N/A 1097 1200 1287
Standby Output (KW) 616 711 731 789 895 970 1089 1227 1429 1429
Aspiration T&A T&I T&A  T&LTA
NO. of Cylinder 12 16
Bore x Stroke (mm) 159×159
Displacement (L) 37.8  50.3 
Compression Ratio 15.5 : 1 13.9 : 1 14.5 : 1 13.9 : 0 13.9 : 1 14.9 : 1
Exhaust Gas Temperature (℃) 521 529 541 477 527 499 529 525 510 510
Rated Fuel Consumption@100% Load (L/h) 140  225  167  154 191  209  256  261  289  309 
Lub Oil Capacity (L) 135 135 177 204 204
Alternator Model JDG354FS JDG404B JDG404B JDG404C JDG404D JDG404E JDG404F JDG404G JDG454B JDG454C
Prime Output (kVA/kW) 625/500 750/600 750/600 800/640 910/728 1000/800 1125/900 1250/1000 1400/1120 1550/1240
Power Efficiency 95.0% 93.2% 93.2% 93.6% 93.5% 94.2% 94.6% 94.8% 95.2% 95.6%
CHARACTERS 4 Pole, Rotating Field,Brushless, Self excited,H class insulation,IP22,AVR460/440 ,12 WINDING LEADS.
Voltage Regulation ±1.0% with4% engine governing
Soundproof Type Dimensions
(LXWXH) m
6058x2438x2590 40' Standard Container
Weight (KG) 8500 8500 8500 8700 8800 9000 10000 12000 13000 13000
Notes: (1)Above based on voltage 220/380V.
(2)The weights are approximate and without fuel.
(3)In line with our policy of continuous product development, we reserve the right to change specification without notice.
(4)N=Natural,T=Turbo-charged,T&CAC=Turbocharged and Charge Air Cooled,T&AAC=Turbocharged,Air-Air Cooled,T&AAA=Turbocharged and Air to Air Aftercooled,T&A=Turbocharged,T&I=Turbo &Intercooler,T&LTA=Turbocharged and Low Temperature Aftercooled & Aftercooled.
Rating Definitions
Prime Power Rating
Applicable for supplying electric power in lieu of commercially purchase power. Prime Power applications must be in the form of one of the following.
Unlimited Time Running Prime Power
Prime Power is available for an unlimited number of hours per year in a varible load application. Variable load should not exceed a 70% average of the Prime. 
Power rating during any operating period of 250 hours.The total operating time at 100% Prime Power shall not exceed 500 hours per year. A 10% overload 
capability is available for a period of 1 hour within a 12-hour period of operation. Total operationg time at the 10% overload power shall not exceed 25 hours 
per year.


PRODUCT INQUIRY